Eaton CF1000(Addressable Single Loop)

Eaton CF1000: The Ideal Fire Control Solution for Resellers/Endusers  in India-Intelligent addressable control panel

Are you a reseller in Mumbai searching for a reliable and advanced fire control panel? Look no further than the Eaton CF1000! This intelligent addressable control panel offers a perfect blend of sophisticated features and user-friendly operation, making it suitable for a wide range of small to medium-sized projects.

Key Features and Benefits:

  • Scalable System: Available in 1-loop (CF1100) and 2-loop (CF1200) versions, accommodating up to 200 addresses per loop.
  • Network Capability: Connect up to 126 panels using Eaton’s network card (NC), enabling comprehensive fire safety coverage for larger establishments.
  • Effortless Installation: Soft addressing simplifies the setup process and eliminates potential errors associated with manual addressing.
  • User-Friendly Interface: The large, versatile touch-screen display facilitates easy operation and monitoring.
  • Multilingual Support: The system offers multi-language selection, catering to Mumbai’s diverse population.
  • Reliable Power: Built-in power supply and batteries ensure continuous operation even during power outages.
  • Flexible Programming: Powerful cause-and-effect programming enables customized system responses to various fire events.
  • Comprehensive Compatibility: A full range of compatible intelligent addressable ancillaries integrate seamlessly with the CF1000.
  • Enhanced Safety: All ancillaries feature built-in short circuit isolators, providing maximum protection against faults.
  • Simplified Design: User-friendly software simplifies system design and cause-and-effect programming.

Technical Specifications:

Table 1: CF1000 Technical Specifications

Feature CF1100 CF1200
Number of loops 1 2
Addresses per loop 200 200
Sounder circuits 2 (monitored, max 1.5A combined) 2 (monitored, max 1.5A combined)
Auxiliary fire routing output 24V DC, 30mA max (monitored) 24V DC, 30mA max (monitored)
Auxiliary fire protection output 24V DC, 30mA max (monitored) 24V DC, 30mA max (monitored)
Auxiliary fault routing output 12V DC, 30mA max (monitored) 12V DC, 30mA max (monitored)
System voltage 24V DC (nominal) 24V DC (nominal)
Mains input 230V AC +10% / -15% 230V AC +10% / -15%
Class change Via external contacts or input interface Via external contacts or input interface
Auxiliary relay Changeover contacts on fire condition Changeover contacts on fire condition
Output ports RS485, RS232 RS485, RS232
Battery 2 x 12V, 7Ah 2 x 12V, 7Ah
Operating temperature -5°C to +40°C -5°C to +40°C
Humidity 0 to 93% (+2/-3%) RH, non-condensing 0 to 93% (+2/-3%) RH, non-condensing
Dimensions (H x W x D) 375mm x 357mm x 95mm 375mm x 357mm x 95mm
Weight 8kg 8kg
Ingress Protection IP30 IP30
Cable entries Top: 20mm knockouts, Back: aperture Top: 20mm knockouts, Back: aperture
Networking Up to 126 panels with network card Up to 126 panels with network card
Standards EN54 Pt2, Pt4, Pt13 EN54 Pt2, Pt4, Pt13

Network Operation:

The CF1000 is designed for seamless integration into networked fire safety systems.

  • Network Card: Each panel requires an additional network card for network connectivity.
  • Network Capacity: A maximum of 126 CF1000 panels can be networked together, providing centralized monitoring and control.
  • Compatibility: The system seamlessly integrates with Eaton’s CF3000 panels, ensuring compatibility and scalability for larger or more complex installations.
  • Repeater Options: Passive (CF3000PRG) and touch-screen (CTPR3000) repeater panels offer flexible monitoring and control options throughout the network.
  • Reliable Communication: Utilizing RS485 and RS232 communication protocols ensures robust and reliable data transmission between networked devices.